HydroXpandHandbook

← HXB-V1 handbook

Maintenance

HXB-V1 · updated 2026-10-01

Daily, weekly and monthly checks, electrolyte replacement, cleaning and reading performance trends.

What to check and how often, when to change the electrolyte, and whether a rising voltage is normal. Decommissioning and storage have their own chapter.

  • DailyLeaks · noise · smell · readings
  • ElectrolyteNo fixed interval · by condition
  • Stack serviceReturn it; we replace the MEA only
How to read this chapter

First timeStart with the daily, weekly and monthly lists and copy them into your own check sheet. Reading performance trends becomes useful a few months in.

Done this beforeGo straight to reading performance trends and deciding when to change the electrolyte.

On this pageThe intervals are guidance, not rules

The intervals are guidance, not rules

The check lists

Daily, or each shift

  • No leaks, wetness, mist or splashing around the tubing, fittings and front-panel connections.
  • No wetness or white crystals on or under the base of the unit. If you see any, stop operating and find the leak. Leaked electrolyte that dries out leaves KOH that can form a conductive path and melt nearby parts.
  • No abnormal noise, vibration or smell.
  • The front-panel LED and the app show normal operation with no active critical alarm.
  • Stack current and voltage are reasonable for the setpoint.
  • Electrolyte level, flow and temperature are within range.
  • The discharge area is clear and ventilated, with no ignition source nearby.

Weekly

  • Look back at the stack voltage at comparable operating points.
  • Check that level, flow and temperature stayed stable.
  • Look for alarms that keep recurring, and their pattern.
  • Inspect hoses and fittings for wear, discolouration, crystal residue and small weeping leaks.
  • Inspect cable routing and connectors for abrasion, looseness and overheating marks.
  • Confirm the tubing supports are not loading the fittings and ports.

Monthly

  • Check the electrolyte for discolouration and solids.
  • Inspect the vent and drain paths for blockage, corrosion and salt build-up, and clean as needed.
  • Clean the ventilation openings and the area around them so dust does not accumulate.
  • Update the maintenance record: running hours, electrolyte change dates, alarms, observations and corrective actions.

Maintenance log

The unit logs operating data, but not electrolyte concentration and changes, the water used, leaks or anything done by hand. Keeping these columns lets us narrow down a cause quickly when something goes wrong. Write one line at every check.

ColumnWhat to writeExample
DateDay of the check2026-10-05
Total run hoursThe value on the control app Home screen312 h
Operating pointCurrent, electrolyte temperature, pressure50 A · 50 °C · 10 barg
Stack voltageMeasured at the same operating point. This column is for the trend41.2 V
ElectrolyteWhether it was changed, the measured concentration and method, colour and foamNot changed · 0.10 M (refractometer) · clear
Feed waterQuality (conductivity) and the day the reservoir was refilled0.8 µS/cm · refilled
Leaks and crystalsBase of the unit, ports and fittings, vent endsNone
AlarmsAlarms raised since the last check and how oftenElectrolyte flowrate low ×1
Action takenAnything done by hand, such as cleaning, part replacement or a setting changeCleaned fan filter
Checked byWho did the check(signature)

Changing the electrolyte

Best practice: measure conductivity regularly

When the KOH concentration falls, the electrolyte's conductivity falls with it. Measuring conductivity regularly therefore tells you the state of the electrolyte before the voltage starts to rise. A conductivity meter is all it takes.

When
Measure once right after filling fresh electrolyte and record it as your baseline. After that, measure once a month.
How
Stop electrolysis and let it cool, put on PPE, and draw a small sample from the DRAIN port into an alkali-resistant container. Read the 25 °C value on a temperature-compensated conductivity meter. At a different temperature the same electrolyte reads differently.
Reference
0.1 M KOH reads about 20–23 mS/cm at 25 °C. Comparing with your own baseline is more reliable than the absolute value.
More than 20% below baseline
Replace the electrolyte and look for the cause under Where electrolyte escapes below. Leave the cause in place and the fresh electrolyte will go the same way.
More than 20% above baseline
Water is short and the electrolyte has concentrated. Check first that water make-up is working. See Water make-up in the Operation and control chapter.
How to decide on electrolyte replacement from conductivity. 1 Right after a fresh fill, measure once and record it as the baseline; 0.1 M KOH reads about 20–23 mS/cm at 25 °C. 2 Then once a month, stop, let it cool, draw a small sample from DRAIN and read the 25 °C value on a temperature-compensated meter. 3 Compare with the baseline. More than 20% low: replace it and find where the electrolyte is escaping. Within ±20%: keep running and measure again next month. More than 20% high: water is short and it has concentrated, so check water make-up first.
Figure 6-1 Deciding replacement from conductivity. The ±20% band is a suggested value; compare with your own baseline rather than the absolute reading.

If you cannot measure conductivity

Replace the electrolyte if you see any of the following. You will find out later than by measuring conductivity, so we recommend getting a conductivity meter where possible.

Voltage creeps up at the same operating point
The electrolyte concentration may have fallen. It looks like stack degradation, but voltage often recovers with fresh electrolyte alone. Measure the concentration before suspecting the stack.
Make-up interval or level behaves differently
If make-up runs more or less often than usual at the same operating point, electrolyte is escaping somewhere or water is short. Compare with the make-up entries in your maintenance log.
Moisture at H2 OUT tests alkaline
During steady operation, touch pH paper to the moisture coming out of H2 OUT. If it tests alkaline, electrolyte is crossing to the hydrogen side. Replace the electrolyte and contact us.
Restarting after a long idle period
While idle, carbon dioxide from the air can dissolve and weaken the electrolyte. If you cannot measure it, replace it before restarting.
Heavy foaming
Electrolyte is carried out through O2 OUT with the foam, so concentration and level both fluctuate. Replace it and watch whether the foam returns. If it does, contact us.
Discoloured or with solids
It is contaminated or something has dissolved into it. Replace it, photograph the drained electrolyte and contact us.
After fixing a leak or replacing parts
While it leaked, KOH escaped and make-up water took its place, so the concentration is already low. Replace all of it once the repair is done.

Where electrolyte escapes

In normal operation the KOH does not decrease. If the concentration falls anyway, KOH is escaping somewhere and the make-up pump is replacing the loss with pure water. There are three ways out.

WhereHow you can tell
Out of the stackA seal between cells is leaking. The stack perimeter or the base of the unit gets wet or grows white crystals. A small leak may never trip the leak sensor and show only as a slow fall in concentration.
Inside the stack, across to the hydrogen sideElectrolyte crosses the membrane from the oxygen side (anode) to the hydrogen side (cathode) and leaves with the hydrogen. Moisture from H2 OUT tests alkaline on pH paper. A fast depressurisation after pressurised operation can give briefly alkaline moisture, so check during steady operation.
From the electrolyte tankThe tank gasket, a joint or a connecting fitting is leaking. The base of the unit gets wet or the electrolyte leak alarm appears. The tank sits inside the enclosure, so unless you are qualified, do not open it; contact us.

In every case, contact us rather than just replacing the electrolyte again and again. Leaks from the stack are handled through stack service.

Cleaning

Exterior

  • Wipe with a cloth dampened with clean water. Never spray liquid onto the system.
  • If needed, use ethanol on painted and metal surfaces only, applied to the cloth, avoiding labels and seams.
  • KOH residue shows up as white crystals: dissolve it with a water-dampened cloth and wipe again with clean water.
  • Do not clean during operation. Stop the system first, especially before wiping near the ventilation openings, connectors or front-panel fluid connections.

Interior

Reading the performance trend

Stack voltage creeps up over time, from electrode and membrane degradation and from operating history. The question is not whether it rises but how.

Can be normal
A slow, steady rise over a long period
Worth investigating
A step change at constant current, a large rise or fall over a short period, especially with the stack or electrolyte temperature climbing too, and large fluctuations at constant current

When it looks wrong, look outside first

  • Whether the electrolyte condition or concentration has drifted
  • The DI water quality and any source of contamination
  • Whether flow and temperature are stable and cooling is working
  • The hydrogen and oxygen routing, backpressure, and anywhere gas gets trapped
  • The sensors and analysers, and the wiring and connections

If it persists after those checks, contact us with the operating history and the trends you recorded.

Decommissioning and storage

What this chapter is based on

Resource library →

TroubleshootingWhat to check first when voltage jumps or pressure and flow become unstable, with causes and actions for four symptoms.

Ask the engineer who built it

If your case is not covered here, send us the operating condition and what you observed. The engineer who designed the system answers directly.