HydroXpandHandbook

← HXB-V1 handbook

Maintenance

HXB-V1 · updated 2026-10-05

Daily, weekly and monthly checks, electrolyte replacement, cleaning and reading performance trends.

What to check and how often, when to change the electrolyte, and whether a rising voltage is normal. Decommissioning and storage have their own chapter.

  • DailyLeaks · noise · smell · readings
  • ElectrolyteNo fixed interval · by condition
  • Stack serviceReturn it; we replace the MEA only
How to read this chapter

First timeStart with the daily, weekly and monthly lists and copy them into your own check sheet. Reading performance trends becomes useful a few months in.

Done this beforeGo straight to reading performance trends and deciding when to change the electrolyte.

On this pageThe intervals are guidance, not rules

The intervals are guidance, not rules#

The check lists#

Daily, or each shift#

  • No leaks or wet marks around the tubing, fittings and front-panel connections.
  • No wetness or white crystals on or under the base of the unit. If you see any, stop operating and find the leak. Leaked electrolyte that dries out leaves KOH that can form a conductive path and melt nearby parts.
  • No noise, vibration or smell that differs from usual. The fan always makes some noise and vibration while running; look for a change from normal.
  • The front-panel LED and the app show normal operation with no active critical alarm.
  • Stack current and voltage are reasonable for the setpoint.
  • Electrolyte level, flow and temperature are within range.
  • The discharge area is clear and ventilated, with no ignition source nearby.

Weekly#

  • Look back at the stack voltage at comparable operating points.
  • Check that level, flow and temperature stayed stable.
  • Look for alarms that keep recurring, and their pattern.
  • Inspect hoses and fittings for wear, discolouration, crystal residue and small weeping leaks.
  • Inspect cable routing and connectors for abrasion, looseness and overheating marks.
  • Confirm the tubing supports are not loading the fittings and ports.

Monthly#

  • Check the electrolyte for discolouration and solids.
  • Inspect the vent and drain paths for blockage, corrosion and salt build-up, and clean as needed.
  • Clean the ventilation openings and the area around them so dust does not accumulate.
  • Update the maintenance record: running hours, electrolyte change dates, alarms, observations and corrective actions.
Print the routine check sheetOne sheet per week: daily items by day, weekly and monthly items below.PDF · A4

Maintenance log#

The unit logs operating data, but not electrolyte concentration and changes, the water used, leaks or anything done by hand. Keeping these columns lets us narrow down a cause quickly when something goes wrong. Write one line at every check.

ColumnWhat to writeExample
DateDay of the check2026-10-05
Total run hoursThe value on the control app Home screen312 h
Operating pointCurrent, electrolyte temperature, pressure50 A · 50 °C · 10 barg
Stack voltageMeasured at the same operating point. This column is for the trend41.2 V
ElectrolyteWhether it was changed, conductivity at 25 °C, colour and foamNot changed · 21.4 mS/cm · clear
Feed waterQuality (conductivity) and the day the reservoir was refilled0.8 µS/cm · refilled
Leaks and crystalsBase of the unit, ports and fittings, vent endsNone
AlarmsAlarms raised since the last check and how oftenElectrolyte flowrate low ×1
Action takenAnything done by hand, such as cleaning, part replacement or a setting changeCleaned fan filter
Checked byWho did the check(signature)
Print the maintenance logThe ten fields above, one block per check, on one A4 sheet. The top block shows an example.PDF · A4

Changing the electrolyte#

Best practice: measure conductivity regularly#

When the KOH concentration falls, the electrolyte's conductivity falls with it. Measuring conductivity regularly therefore tells you the state of the electrolyte before the voltage starts to rise. A conductivity meter is all it takes.

When
Measure once right after filling fresh electrolyte and record it as your baseline. After that, measure once a month, always at the same point: just after a water make-up has finished is best. Between make-ups the water level drops and the electrolyte concentrates, so readings taken at random times vary widely even for the same electrolyte.
How
Stop electrolysis and let it cool, put on PPE, and draw a small sample from the DRAIN port into an alkali-resistant container. Read the 25 °C value on a temperature-compensated conductivity meter. At a different temperature the same electrolyte reads differently.
Reference
0.1 M KOH reads about 20–23 mS/cm at 25 °C. Comparing with your own baseline is more reliable than the absolute value.
Below half the baseline
Replace the electrolyte and find the cause. The most common one is electrolyte crossing the membrane to the hydrogen side: touch pH paper to the droplets from H2 OUT, and if it reads alkaline this is the case. A wet base, or wetness or white crystals around the stack, means it is leaking out. See Where electrolyte escapes below. Leave the cause in place and the fresh electrolyte will go the same way. In our concentration test (2 kW stack, 50 A), halving the concentration raised the stack voltage by about 1 V (about 2.5%).
Above that
Keep running and measure again next month. If it keeps falling month after month, though, KOH is escaping somewhere: check Where electrolyte escapes below before it reaches half.
Make-up more frequent than usual
A sign that electrolyte has started to escape. The make-up pump replaces what is lost with water, so make-up becomes more frequent and the conductivity drifts down as a result. It shows before the conductivity reaches half, so check the pH of the H2 OUT droplets and the base and stack surroundings now, and contact us.
How to decide on electrolyte replacement from conductivity. 1 Right after a fresh fill, measure once and record it as the baseline; 0.1 M KOH reads about 20–23 mS/cm at 25 °C. 2 Then once a month, at the same point just after a make-up, stop, let it cool, draw a small sample from DRAIN and read the 25 °C value on a temperature-compensated meter. 3 Compare with the baseline. Below half the baseline: replace it and find where the electrolyte is escaping. Above that: keep running and measure again monthly. If it keeps falling month on month, look for the leak.
Figure 7-1 Deciding replacement from conductivity. Compare with your own baseline rather than the absolute reading. The points on the graph are illustrative.
Print the electrolyte logBaseline, the replacement line (half) and monthly readings on the front; change records and replacement signs on the back.PDF · A4

If you cannot measure conductivity#

Replace the electrolyte if you see any of the following. You will find out later than by measuring conductivity, so we recommend getting a conductivity meter where possible.

Voltage creeps up at the same operating point
The electrolyte concentration may have fallen. It looks like stack degradation, but voltage often recovers with fresh electrolyte alone. Measure the concentration before suspecting the stack.
Make-up interval or level behaves differently
If make-up runs more or less often than usual at the same operating point, electrolyte is escaping somewhere or water is short. Compare with the make-up entries in your maintenance log.
Moisture at H2 OUT tests alkaline
During steady operation, touch pH paper to the moisture coming out of H2 OUT. If it tests alkaline, electrolyte is crossing to the hydrogen side. Replace the electrolyte and contact us.
Restarting after a long idle period
While idle, carbon dioxide from the air can dissolve and weaken the electrolyte. If you cannot measure it, replace it before restarting.
Heavy foaming
Electrolyte is carried out through O2 OUT with the foam, so concentration and level both fluctuate. Replace it and watch whether the foam returns. If it does, contact us.
Discoloured or with solids
It is contaminated or something has dissolved into it. Replace it, photograph the drained electrolyte and contact us.
After fixing a leak or replacing parts
While it leaked, KOH escaped and make-up water took its place, so the concentration is already low. Replace all of it once the repair is done.

How to change it#

Have about 5 L of fresh 0.1 M KOH solution (made the same way as in the quick-start chapter), an alkali-resistant container for the old electrolyte, 1/4″ tubing to fit to DRAIN, safety glasses and alkali-resistant gloves ready.

  1. Stop electrolysis.
    • Set Power Control to OFF and confirm the current falls to 0 A.
  2. Set Electrolyte Control to OFF.
    • Left on, the make-up pump draws water back in through H2O IN as the level drops.
    • Mains power can stay on. DRAIN connects to the electrolyte loop only.
  3. With the container under DRAIN, remove the cap, push 1/4″ tubing fully home and tighten the nut, leading the tubing into the container.
    • DRAIN is the same 1/4″ double-ferrule fitting as the other ports and has no valve. It flows the moment the cap is off, so have the tubing and nut in hand before you start.
  4. Drain until the flow stops.
    • A little liquid left in the stack and tubing is normal.
    • If notIf the flow stops partway, check that the tubing is not kinked and is pushed fully home.
  5. Undo and remove the tubing, then refit and tighten the DRAIN cap.
  6. Fill and prime with fresh electrolyte, exactly as in “Fill and prime the electrolyte” in the quick-start chapter.
    • Put the end of the H2O IN tube into the fresh electrolyte, then switch Electrolyte Control ON with flow at 0 and temperature at room temperature. When the tank is two-thirds full, set the flow to 4 L/min; when it is full, move the H2O IN tube back to the purified-water container.
    • Do not put the old electrolyte back or mix it with the new.
  7. Check DRAIN and the front ports for leaks.
    • CheckThe ports and fittings are dry.
    • If notIf it leaks, switch Electrolyte Control off, retighten that fitting and check again.
  8. Take a new baseline.
    • The conductivity straight after the new fill is the baseline for the next decision (step 1 of figure 7-1 above).
  9. Record it.
    • Write the date, the state of the old electrolyte (colour, solids) and the new baseline on the electrolyte log.

Do not pour the old electrolyte down the drain; dispose of it under your site's chemical waste procedure.

Where electrolyte escapes#

In normal operation the KOH does not decrease. If the concentration falls anyway, KOH is escaping somewhere and the make-up pump is replacing the loss with pure water. There are three ways out.

WhereHow you can tell
Out of the stackA seal between cells is leaking. The stack perimeter or the base of the unit gets wet or grows white crystals. A small leak may never trip the leak sensor and show only as a slow fall in concentration.
Inside the stack, across to the hydrogen sideElectrolyte crosses the membrane from the oxygen side (anode) to the hydrogen side (cathode) and leaves with the hydrogen. Moisture from H2 OUT tests alkaline on pH paper. A fast depressurisation after pressurised operation can give briefly alkaline moisture, so check during steady operation.
From the electrolyte tankThe tank gasket, a joint or a connecting fitting is leaking. The base of the unit gets wet or the electrolyte leak alarm appears. The tank sits inside the enclosure, so unless you are qualified, do not open it; contact us.

In every case, contact us rather than just replacing the electrolyte again and again. Leaks from the stack are handled through stack service.

Cleaning#

Exterior#

  • Wipe with a cloth dampened with clean water. Never spray liquid onto the system.
  • If needed, use ethanol on painted and metal surfaces only, applied to the cloth, avoiding labels and seams.
  • KOH residue shows up as white crystals: dissolve it with a water-dampened cloth and wipe again with clean water.
  • Do not clean during operation. Stop the system first, especially before wiping near the ventilation openings, connectors or front-panel fluid connections.

Interior#

Reading the performance trend#

Stack voltage creeps up over time, from electrode and membrane degradation and from operating history. The question is not whether it rises but how.

Can be normal
A slow, steady rise over a long period
Worth investigating
A step change at constant current, a large rise or fall over a short period, especially with the stack or electrolyte temperature climbing too, and large fluctuations at constant current

When it looks wrong, look outside first#

  • Whether the electrolyte condition or concentration has drifted
  • The DI water quality and any source of contamination
  • Whether flow and temperature are stable and cooling is working
  • The hydrogen and oxygen routing, backpressure, and anywhere gas gets trapped
  • The sensors and analysers, and the wiring and connections

If it persists after those checks, contact us with the operating history and the trends you recorded.

Decommissioning and storage#

What this chapter is based on

Resource library →

TroubleshootingWhat to check first when voltage jumps or pressure and flow become unstable, with causes and actions for four symptoms.
Was this page helpful?

Ask the engineer who built it

If your case is not covered here, send us the operating condition and what you observed. The engineer who designed the system answers directly.