← Components & BoP
Downstream

Hydrogen drying and purification

Moisture and oxygen removal downstream of the electrolyser

Hydrogen leaving the electrolyser is water-saturated. We define the downstream train to meet the dew point and purity your application requires. Our modular dryer HXD-V1 is in development.

Until HXD-V1 launches we run this as a specification and quotation desk.

WaterTreatmentCirculationCell / stackDryingAnalysisCompression
Dew point basis
We quote on an atmospheric basis. We convert to line pressure on request
Purity basis
99.999 percent = total impurities at or below 10 ppmv (water, oxygen and nitrogen combined)
Validated result
At least 99.999 percent with a dryer fitted; O₂-in-H₂ maximum 0.10 percent over 2,400 hours on a 23-cell HXS-2
Understand

What this part does and what decides it

Why it matters

The main impurity in hydrogen leaving the electrolyser is water. On HXB-V1, purity is 98 to 99 percent without a dryer and above 99.999 percent with one. Most of that gap is water vapour. That remaining moisture is quoted as a dew point: the temperature at which dew starts to form as the gas is cooled. Less water means the gas has to go colder before dew appears, so a lower dew point means drier. It is not the temperature the equipment runs at; it is a moisture figure written as a temperature. Raising the pressure raises the dew point for the same amount of water, so every figure we quote is at atmospheric pressure. Our stacks circulate KOH on the anode side only, so the hydrogen line carries moisture and trace oxygen and nothing else. The outlet gas is saturated, so it condenses as it cools in the piping, and removing oxygen as well adds heat from the catalyst. That is why two applications with the same purity target can need different trains.

IN OUR OWN SYSTEMS

HXB-V1 delivers hydrogen at 0 or 10 barg through a 1/4 inch double-ferrule outlet. Under our validated conditions, purity of at least 99.999 percent was confirmed with a dryer, and oxygen on the hydrogen side (O₂-in-H₂) reached a maximum of 0.10 percent over the 2,400 hour run on a 23-cell HXS-2.

Dew point (atmospheric)Total impurity
0 °CBounded by the freezing point
-40 °C
About 128 ppmv
10 ppmv — the 99.999% allowance
-60 °CWater alone is already past it
About 10.7 ppmv
-70 °CCompatible with 99.999%
About 2.6 ppmv
Below this point the axis is total impurity, not dew point
ppb level
Cooling and condensing
Adsorption (PSA, TSA)
Purification (getter, palladium membrane)

Spacing shows order only; it is not to scale.

Background

What is actually in the hydrogen

What leaves the stack during operation is moisture and trace oxygen. Nitrogen is not made by the stack; it enters from purge gas and air left in the pipework.

Moisture
The outlet gas is saturated. This is most of what the purity figure measures
Oxygen
Trace crossover from the anode. Fuel cell and refuelling specifications set a limit on it
Nitrogen
Enters from purge and residual air. It shows up at start-up and after maintenance, and does not grow during operation

Dew point and purity are different quantities

99.999 percent means total impurities, water and oxygen and nitrogen together, at or below 10 ppmv. Dew point describes water alone. Using one figure in place of the other produces the wrong specification. The conversions below are on an atmospheric basis. At -70 °C water uses only a quarter of the total allowance, so it is compatible with 99.999 percent and oxygen removal covers the rest. At -60 °C water alone is already past 10 ppmv: removing every trace of oxygen still would not reach 99.999 percent, so an application with that requirement has to dry further.

Dew point -40 °C
About 128 ppmv — enough to stop condensation, short of 99.999 percent
Dew point -60 °C
About 10.7 ppmv — water alone is already past the 10 ppmv allowance, short of 99.999 percent
Dew point -70 °C
About 2.6 ppmv — compatible with 99.999 percent

A dew point is stated with its pressure

-40 °C at atmospheric pressure and -40 °C at 10 barg are entirely different conditions. If you need a figure at line pressure we will convert it. One more reference point has to be agreed. The dryer outlet dew point is not the dew point at your point of use: moisture held on the pipe walls desorbs downstream and the reading there is higher. The longer the run, and the longer the system has stood idle, the wider that gap.

The methods available

The downstream train is not a choice between methods so much as a stack built to the requirement. The layers are below. An application that only needs a lower dew point stops after the first one or two; an application with a purity figure adds the later ones. Of these, the only layer we can source today at this scale is palladium membrane purification. The rest either go into the HXD-V1 design or have no market product this small. That is why the table below is short.

Cooling and condensation
Chills the gas so water drops out as liquid. The simplest and cheapest arrangement, limited to a dew point near 0 °C by the freezing point of water. It earns its place by reducing the load on whatever follows
Adsorption, pressure swing (PSA)
Water is held on an adsorbent, then driven off by dropping the pressure, with two vessels alternating. Regeneration needs no heat and is quick, but some product gas leaves with the purge, so hydrogen is lost
Adsorption, temperature swing (TSA)
The same adsorption regenerated with heat instead of pressure. Regeneration takes longer and the heater draws power, but almost no product gas is discarded. This is the side to look at when hydrogen loss matters at small scale
Catalytic deoxo
Reacts the remaining oxygen with hydrogen to form water. The oxygen becomes moisture, so drying always follows. The reaction gives off heat, so cooling comes into the picture when the inlet oxygen is high
Getter (chemical absorption)
A heated metal chemically binds oxygen, moisture and nitrogen. It reaches ppb level and discards no hydrogen. What it binds it does not release, so the unit is replaced outright at end of life
Palladium membrane purification
Only hydrogen atoms cross a heated palladium membrane, leaving everything else behind and taking total impurities to ppb level. The membrane has to be held at around 400 °C, and gas that does not cross is vented, so recovery is lower
Polymer membrane separation
Separates on the difference in how fast species cross a membrane. Easy to run continuously and free of consumables, but the separation is incomplete so the achievable purity is limited. It belongs where continuity matters more than purity
Choose

The options and the models we handle

What you can choose

Start here and we adjust to your conditions. We can usually source what is not listed.

Dew point controlPreventing condensation in downstream piping and storage

Moisture only. If the point is to stop water collecting downstream, this is far enough.

Quote this option
DryingProcess supply and analysis

Moisture down to ppm level. Most of what separates 99 percent purity from higher is water vapour.

Quote this option
Drying with oxygen removalFuel cells and refuelling

Moisture and trace oxygen together. Needed where an oxygen limit applies.

Quote this option

The train follows from the dew point and purity you need. Tell us the application and we will work out which of these it lands on.

Models we can source

General-purpose industrial hydrogen dryers typically start around 5 Nm³/h, and even the small units built for electrolysers stop at about 1 Nm³/h. A single HXB-V1 produces 0.5 Nm³/h. That gap is why we are building HXD-V1. Below are the candidates that do fit that scale.

Our own, in development — if you can wait

ModelMethodOriginQuote this
HydroXpandHXD-V1
Multi-layer trainKorea (made by us)Quote this item

Available now — palladium purification

ModelMethodThroughputOutlet purityOriginQuote this
SAES Pure GasPE-2100
Palladium membrane purification6 · 14 · 30 slpmTotal impurities below 1 ppbUnited StatesQuote this
EntegrisMegaTorr PS7-PD05
Palladium membrane purification0 – 50 slpm (about 3 Nm³/h)Total impurities below 1 ppbUnited StatesQuote this
Order

What to settle before a quotation

What often goes wrong

Only what has come up more than once in real enquiries.

How clean does it need to be

What dew point comes out of the dryer?

The target dew point has to be set first, because it decides the train. When you set it, tell us two things alongside it: whether the figure is on an atmospheric or a line-pressure basis, and whether it applies at the dryer outlet or at your point of use. Without those two, the same number describes different conditions to each of us.

Does our application need oxygen removal as well?

It comes down to whether your application sets an oxygen limit. Fuel cells and refuelling usually do; process supply and analytical use often need only the moisture figure met. Send us the specification if one applies, and if none does, just telling us the application is enough for us to work out which side it lands on.

What should we buy

Is a dryer included with HXB-V1?

Not in the standard configuration. Purity of at least 99.999 percent was confirmed under our validated conditions with a dryer fitted. If you need one before HXD-V1 launches, we supply a dryer matched to your conditions. We carry the overseas purchase and customs clearance, invoice you domestically, and pass the manufacturer warranty through to you.

How does the palladium purifier in the table differ from a dryer?

A dryer deals with moisture alone; a palladium purifier passes hydrogen and leaves everything else behind. What each one costs you is set out above under the methods section. The rule for choosing is simple: if all you need is a lower dew point, a purifier is more than the job requires.

Should we wait for HXD-V1?

It depends on when you need the hydrogen. HXD-V1 is targeting Q4 2026 and its specification is not yet fixed, so we cannot quote it today. If you need hydrogen before then, choosing from the models we can source is the better route. If your timing has room, we will send you the specification as soon as it is settled.

If several units run in parallel, do we need one dryer per unit?

No. The outlets join one shared hydrogen pipe and the dryer and storage are shared. Tell us the combined flow and the maximum number of units running at once and we will size against that.

What we confirm before quoting

Once these are set, selection and quotation happen in one step. If they are not, we start there.

  • Required dew point and purity
  • Flow rate and operating pressure
  • Application: fuel cell, analysis, process or refuelling
  • Country of installation

Supply terms

Our own product
HXD-V1 in development, targeting Q4 2026
Until launch
We source a dryer matched to your conditions
Scope of supply
Selection, sourcing and domestic delivery
Warranty
Sourced items carry the manufacturer warranty through to you
Specification basis
Figures in the table follow published manufacturer data. We re-confirm the current specification before ordering

Send us the checklist

Fill in only what you know. We ask about the rest.

Request a quote for this item