HydroXpandHandbook

← HXB-V1 handbook

Downstream

HXB-V1 · updated 2026-09-30

What leaves the outlet, what to check when you attach a dryer or a compressor, routing that avoids backpressure, and downstream measurement.

This chapter starts where the hydrogen leaves H2 OUT. What comes out and in what state, what you stack on top of it for your application, and the conditions the system itself imposes when you attach something.

The drying and purification layers, what each one does, and the models we can source today are set out on the components pages. This chapter covers only the HXB-V1 side and the order in which to decide.

  • ScopeFrom H2 OUT to the point of use
  • When to readBefore you order, and before you install
  • Decide firstThe dew point, purity and pressure your application needs
How to read this chapter

First timeWrite down what your application requires as numbers, then read from the first section. Look at what comes out before deciding what to attach.

Done this beforeCheck just the backpressure section and the measurement section. Those two are what usually catch you when you change the downstream.

On this pageWhat leaves the outlet

What leaves the outlet

Downstream design starts from these figures. All of them are without a dryer attached.

ItemFigureWhat it means downstream
FlowUp to 480 NL/h0.48 Nm³/h, about 8.0 NL per minute. Downstream equipment is usually rated in these units.
Pressure0 barg or 10 bargSelected in software. 10 barg is the ceiling; anything above it is the downstream compressor's job.
Purity98–99% at 0 barg · 99% at 10 bargMost of the balance is water. With a dryer it is 99.999% or better.
MoistureSaturatedIt condenses in the pipework and vessels as the gas cools. That is what pools at the low points.
Port1/4-inch double ferruleAll five ports (H2O IN, H2 OUT, O2 OUT, H2 VENT, DRAIN) use the same fitting.

What to decide first

The downstream is not a choice between methods but a stack of layers built to a requirement. Fix what the application demands as numbers first, and the number of layers follows.

  1. Write down the dew point and purity the application requires, as numbers.
    • Use the figures from the specification if you have one; if not, tell us what it is for. The application alone is usually enough for us to narrow it down with you.
  2. Write down the pressure you need.
    • If the pressure at the point of use differs from the storage pressure, note both. This decides whether you need a compressor at all, and whether to run the system at 0 or 10 barg.
  3. Decide whether you store it or use it as it is made.
    • Storing brings compression and vessels with it, plus the overpressure protection and permitting the code requires. Using it as produced turns the question into whether the application tolerates a varying flow.
  4. Decide how many units and add up the flow.
    • Downstream equipment is selected on the combined flow. One unit is 0.48 Nm³/h, and if you plan to add units later it is better to size for that from the start.
  5. Then build the layers.
    • An application that only needs a lower dew point stops after one or two layers. One that sets a purity target adds the later ones.
ApplicationWhat it usually requiresThe train it needs
Stopping condensation in pipes and vesselsA dew point onlyOne or two front layers that only remove water
Process supply and analysisWater down to ppm levelDrying
Fuel cells and refuellingBoth water and trace oxygenDrying plus oxygen removal

Attaching drying and purification

Scale is the first obstacle. A single HXB-V1 produces 0.48 Nm³/h. General-purpose industrial hydrogen dryers typically start around 5 Nm³/h, and even the small units built for electrolyzers stop at about 1 Nm³/h. Products that fit this band are scarce, which is why we are building the HXD-V1 modular dryer.

What to check

  • Whether the rated flow covers this scale. A model with a minimum flow will not run properly at 0.48 Nm³/h.
  • The inlet pressure it needs. Dryers that run at ambient and dryers that assume a pressurised feed are different machines.
  • The pressure drop. That figure becomes backpressure at the system outlet.
  • How it regenerates. Pressure-swing regeneration vents some product gas each cycle, and at a small flow that loss weighs more.
  • Consumables and their intervals. Adsorbents and getters are parts you replace when they are spent.
  • Certification in the country of installation. Establish first whether the location calls for an explosion-proof rating.

Compression and storage

The compressor sets what has to come before it. Each one has a minimum suction pressure, and if the upstream cannot deliver it the compressor will not run. This is the real reason to choose between 0 and 10 barg on the system.

ExampleMinimum suctionWhat the system must do
Air-driven, two stage, double acting5 barAmbient operation will not drive it. You have to select 10 barg.
Air-driven, single stage, double acting1.7 barAmbient operation still falls short. Without a boost ahead of it, 10 barg is required.

What storage decides

Overpressure protection
When you connect the hydrogen outlet to downstream or storage equipment, provide overpressure protection to your code and design. The protections inside the system do not protect your equipment.
Permitting and installation
High-pressure gas permitting and site installation stay with the site owner. What we can handle also changes with the storage pressure and capacity.
The manufacturer's warranty
Compressors and vessels we source come with the manufacturer's warranty unchanged. We also carry the overseas purchase and customs.

Do not create backpressure

This is the most common problem introduced by adding a downstream. Narrow or block the path out and the pressure pushes back into the system.

  • Fit no valve and nothing that can block on the vent and relief lines. They have to stay open.
  • Do not run with a downstream valve closed. Confirm the path is open before start-up.
  • Do not kink or pinch the tubing, and keep it free of debris and residue.
  • Put a drain or water trap at the low point. The outlet gas is saturated and pooled water will block the line.
  • Watch for freezing. Vent and relief lines holding condensate can freeze shut. Use slope, drain points, insulation or heat tracing as your site requires.
  • Keep objects away from in front of the vent outlets.

What to measure, and where

There is no hydrogen purity analyser inside the system. Downstream quality has to be measured downstream, and where you measure decides the number.

MeasurementWhereWhy there
Dew pointAt the point of useThe dryer outlet dew point is not the dew point at the point of use. Moisture held on the pipe walls desorbs downstream and reads higher there. The longer the run, and the longer it stood idle, the wider the gap.
Oxygen in hydrogenWhere the specification appliesThe order of magnitude decides the instrument. Establish first whether you manage this in ppm or only need percent-level confirmation.
PressureAt the system outlet and at the point of useThe difference between the two is the downstream pressure drop, and it is how you notice backpressure appearing.
FlowAt the system outletThis is the reference point for production. Measured after the dryer, the figure has the regeneration loss taken out of it.

The oxygen outlet

This is the side people forget when planning a downstream. Splitting water produces oxygen too, half the hydrogen by volume.

  • Route O2 OUT to its own safe, well-ventilated discharge point.
  • Never combine it with a hydrogen line or vent. It needs a separate discharge point.
  • An oxygen-enriched atmosphere raises the fire risk. Keep combustibles away from the discharge area.
  • The oxygen stream is saturated too. Keep water from pooling at the low points.

The boundary, once more

Everything in this chapter belongs to your site. We can source it for you, but the design responsibility and the permits stay with the site owner.

What the system does
It delivers hydrogen to H2 OUT at the selected pressure and flow, and relieves pressure through H2 VENT in abnormal conditions.
What your site does
Vent and exhaust routing, drying and purification, compression and storage, the connection to the point of use, downstream instrumentation, and whatever overpressure protection and permits the code requires.
Where we can help
Give us the conditions and we will settle the configuration with you and source it. We also carry the overseas purchase and customs.

What this chapter is based on

Resource library →

TroubleshootingWhat to check first when voltage jumps or pressure and flow become unstable, with causes and actions for four symptoms.

Ask the engineer who built it

If your case is not covered here, send us the operating condition and what you observed. The engineer who designed the system answers directly.