← Blog

Between one and fifteen kilograms a day: parallel units or a bigger stack

2026.09.25

Electrolyzer product grades are not closely spaced. Ours step from about 1 kg a day to a 15 kg design, and most enquiries land somewhere in between. Repeating the small unit fills that range, and what it actually changes is operation rather than output.

Between one and fifteen kilograms a day: parallel units or a bigger stack

Sizing conversations usually stall at the same place. The quantity of hydrogen the site needs sits above what one unit makes and well below the next grade, and nothing in the catalogue lands on it.

Electrolyzer grades are not closely spaced, and the reason is that a stack is redesigned rather than stretched. Our own steps show it plainly: HXB-V1 produces 480 NL/h, roughly 1 kg a day, and HXS-30 is a 6,900 NL/h design, 15 kg a day. That is a factor of fifteen with nothing between.

Demand of 3, 5 or 10 kg a day sits inside that gap. So does most on-site production for small mobility fuelling, and most continuous low-volume industrial use. The way to fill it is to repeat a unit that already exists rather than wait for one that does not.

1 kg/dayHXB-V1, one unit480 NL/h at the rated point
15 kg/dayHXS-30, design value6,900 NL/h, 46-cell full stack
15×The gap between the two gradesFilled by repeating the smaller unit

What repeating a unit buys

Five units and one larger machine can produce the same quantity. What separates them is not output, it is what happens on the days the plant is not running normally.

A single large machine taken out for service takes production to zero. With five units, removing one leaves four running. That matters to us specifically because stack servicing means the stack comes back to us, so there is a period when that unit is out; in a multi-unit arrangement, supply continues through it.

Capacity can also follow demand rather than anticipate it. The same unit is added later, so the plant starts at the demand that is certain and grows by units. HXB-V1 is a 19-inch rack format, so growing usually means adding to the rack rather than rearranging the room.

And when the available power falls, which happens daily on a renewable-coupled site, the response is to shut units down and match the total with how many are running, rather than to run everything at a low load. Low load is where gas purity headroom is thinnest, so having the option to leave the running units at a load you have measured data for is worth more than it first appears.

Five units and one larger machine make the same hydrogen. They behave differently on the day one of them is out.

What it costs

Two things grow with the unit count, and both are ordinary rather than surprising.

First, connections. Every unit needs water in, hydrogen out, oxygen out, vent and drain, plus its own power feed and its own network cable. HXB-V1 draws about 2.4 kW each, so five units ask the site for that much times five. The network side is light, one cable per unit into a switch, but the cabling still exists per unit.

Second, footprint. Each unit is 482 × 647 × 266 mm and 51.3 kg, and needs 300 mm in front and 400 mm behind. Racking recovers floor area but not height or access. The 5 to 45 °C indoor condition and the site's ventilation arrangements apply to the room regardless of how many units are in it.

There is also a per-unit overhead that is easy to miss on a spreadsheet. Power conversion, the circulation pump and instrumentation sit inside each unit. On HXB-V1 that balance of plant is 0.4 kW of the 2.4 kW total, and it repeats with every unit, where a single larger machine provides it once. Whether that matters depends on the duty cycle, so it belongs in a comparison of total consumption at the design stage rather than in a rule of thumb.

Parallel small unitsOne larger machine
Production during serviceContinues on remaining unitsZero
Adding capacity laterAdd the same unitReplace or add a second machine
Falling available powerShut units down, keep the rest at a measured loadRun the single machine at low load
ConnectionsPer unitwater, gas, vent, drain, power, networkOnce
Balance of plant0.4 kW per unitrepeats with every unitOnce
FootprintGrows with unit countrack recovers floor, not accessSingle location

How the arrangement actually looks

We proposed a ten-unit parallel arrangement to an overseas customer, and the shape of it is worth describing because it is less complicated than the unit count suggests.

Hydrogen outlets are collected. Each unit feeds a common header, and drying and storage sit downstream of that header and are sized once for the plant. Those do not repeat per unit.

Water is not collected. Each unit has an internal gear pump that draws from the customer's tank and tops itself up, so there is no external feed pump to specify.

Operation runs from one laptop. Each unit takes a network cable to a switch, and the desktop application's multi-unit screen issues both plant-wide commands and individual control. No unit is a master; each one is a complete generator and the coordination is in software.

Power arrives per unit as single phase, 200 to 240 V, about 2.4 kW each.

In a parallel arrangement only part of the plant multiplies with the unit count
In a parallel arrangement only part of the plant multiplies with the unit count

What is left as genuine design work is the header: its diameter, and pressure balance between units. HXB-V1 selects 0 or 10 barg in software per unit, so every unit is set to the same pressure before the header joins them, and the storage downstream is what decides which.

Where the parallel approach stops

Repeating a unit has a limit, and there are three separate ways to reach it.

By quantity: above roughly 15 kg a day you are looking at more than fifteen 2 kW units, and a design built on HXS-30 becomes easier on both piping and floor area. The 46-cell full stack is available now, under long-term evaluation after its first operation. A 30 kW system as a finished product is roadmap, not a current specification.

By site requirement: some projects need a single skid, or have a fixed footprint that a growing unit count does not fit. That points at the larger stack regardless of quantity.

By software: the multi-unit control is designed for up to 50 units. We have not run that many simultaneously, so treat it as a design limit rather than a demonstrated one, and anything in the tens of units deserves its own conversation about operating evidence.

Between about 1 and 15 kg a day, repeat the 2 kW unit. Above that, the unit to repeat becomes the 30 kW stack.

Four things to settle before choosing a size

  1. Daily quantity and operating hours. Hourly output multiplied by hours gives the daily figure, so how many hours a day the plant can run is what sets the unit count. On a renewable-coupled site, the generation profile replaces this number.
  2. Whether production can stop. If supply cannot be interrupted, size one unit above the requirement. If it can, size to the requirement.
  3. Expansion. If demand may grow, reserve the rack space, the header capacity and the electrical headroom now, even if the units come later.
  4. Site and power. Floor area, clearances, ventilation, and whether the building's circuits carry 2.4 kW per unit at the final count.

Those four are worth settling whoever you buy from. Tell us the required flow and the daily operating hours and we will propose a unit count and an operating range together, which is a more useful starting point than a quotation against a capacity figure alone.

Related

Frequently asked questions

Should I buy several small electrolyzers or one larger stack?

Between about 1 and 15 kg per day, repeating the 2 kW unit fills the range. Above that, the unit to repeat becomes the 30 kW stack.

What does running units in parallel change?

Operation rather than output. Five units and one larger machine make the same hydrogen, but they behave differently on the day one of them is out, and they handle a falling load differently.

How far apart are the HydroXpand product grades?

The HXB-V1 makes about 1 kg per day at 480 NL/h and the HXS-30 is designed for 15 kg per day at 6,900 NL/h, a 15-fold gap.