← HXS-2 productGuides / Stack integration

What you need to run an HXS-2 on your own balance of plant

HX-SIG-HXS2-EN-001 · Rev 02 · 2026-08-23

A design reference for integrators who buy the bare stack and build the power supply, electrolyte circulation, gas handling, instrumentation and interlocks themselves. It gives the sizing rationale, the measured figures, and the items we have not fixed yet.

HXS-2 is a stack. You build the power supply, electrolyte circulation, gas handling, instrumentation and interlocks around it. This document gives you the numbers and the structure that design needs.

Which document to read when

DatasheetSpecifications and measured performance curves. While you are evaluating the purchase
This guideBoP sizing rationale, instrumentation and interlock design. While you are designing
User manualPort connections, commissioning, maintenance, troubleshooting. After delivery. ver2.2, 48 pages
Assembly guideUnpacking, disassembly and re-assembly bolting procedure. 8 pages
Warranty and service policyWarranty scope and exclusions, MEA replacement criteria, handling procedure

Design inputs

ItemRecommendedLimit
Operating current50 A80 A maximum
Stack voltageapprox. 40 V (BOL)50.6 V maximum · 2.2 V/cell × 23 cells
Electrolyte0.3 M KOH in DI waterKOH purity 95% or higher · no fixed replacement interval
Electrolyte temperature60 °Croom temperature to 80 °C
Circulation flow4 L/min1 to 10 L/min
Hydrogen-side pressure0 barg10 barg maximum
Feed waterASTM D1193 Type II1.0 µS/cm or below · make-up 0.42 L/h @ 50 A
Cells · active area23 cellsanode 100 cm² · cathode 79 cm²

Performance curves are measured at 0.1 M KOH and 50 °C. If we have given you project-specific conditions, apply those for the first test instead.

Process schematic

The minimum arrangement of the electrolyte loop and the hydrogen line. This is a concept diagram and does not replace a P&ID.

  • Feed runs from the tank through the filter, pump and heat exchanger into the stack IN port. Keep the pump below the tank liquid level.
  • OUT is a wet discharge carrying oxygen and electrolyte together, so it passes through gas-liquid separation and returns to the tank. Measure anode pressure and outlet temperature on this run.
  • The two hydrogen ports are joined and routed to the back-pressure regulator. We recommend a pressure gauge upstream and downstream of the BPR.
  • Do not place any valve that can shut off on the tank vent or the O₂ vent.

Ports and connections

INElectrolyte inlet · 3/8″ double-ferrule
OUTOxygen and electrolyte wet discharge · 3/8″ double-ferrule
H₂ (two ports)Hydrogen outlet · 1/4″ double-ferrule each
DC terminalsM6 threaded terminals · tightening torque 4 to 6 N·m
Rated outputHydrogen approx. 500 NL/h @ 50 A. Oxygen is half that
Make-up waterapprox. 0.42 L/h @ 50 A
Size · weight190 × 210 × 215 mm · 19 kg
  • Port markings follow the engraving on the stack. Layout can differ between revisions, so check the physical engraving first.
  • Support piping and cables separately so their weight does not rest on the ports and terminals.
  • Size DC cable for 50 A continuous and keep terminal torque between 4 and 6 N·m. Over-torque damages the terminal.
  • The stack weighs 19 kg. Use two people or a lift.

Electrolyte loop

Three things have to be settled in the loop: flow, pump head and wetted-part materials.

Recommended flow4 L/min (allowed 1 to 10 L/min)
Stack pressure dropapprox. 0.11 bar at 4 L/min. Measured on the stack alone
Pump selection basisVariable-speed pump with at least approx. 0.3 bar available head at 4 L/min
Speed commandA 24 VDC BLDC driven by 0–5 V or PWM is sufficient. Equivalent schemes are fine
  • 0.11 bar covers the stack only. Add filter, heat exchanger, flow meter, valve and piping losses to arrive at the final head.
  • 0.3 bar is a preliminary selection basis, used before the P&ID and the full loss calculation. It is not a guaranteed final head.
  • Install the pump below the tank liquid level for flooded suction. Do not use it to pressurise the anode loop.
  • Wetted-part materials must be confirmed compatible by the component supplier at your concentration, temperature and design margin.
  • Electrolyte is distributed in parallel to each cell from a common anode manifold. It is not in series.
  • If you run fewer cells, scale the flow proportionally: 4 L/min for 23 cells means roughly 2 L/min for 12. The per-cell current range is unchanged.
If you are considering a higher flow than standard

Raising the flow increases the pressure drop across the stack, widens the anode-to-cathode pressure difference and pushes crossover up. The bottleneck is the internal flow field, which is multi-channel and does not reduce to a single number. Splitting the electrolyte loop is the alternative. This is outside our validated range, so we do not commit to flow or performance figures there.

Requests to change the internal flow field

The bipolar plate is formed in a die, so changing the flow field means cutting a new die. It is not a practical option. If you need to explore it, we will share drawings and go through it on a call.

Heat to remove

Heat load is the input power minus the chemical energy carried away as hydrogen. The figures below are calculated from Faraday's law and the higher heating value. They are not measured.

Rated50 A · 40 Vinput 2.0 kW · hydrogen 43 g/h · 1.7 kW on an HHV basis
Rated heat loadapprox. 0.3 kWthe difference between the two figures above
Operating limit80 A · 50.6 Vinput 4.1 kW · hydrogen 69 g/h · 2.7 kW on an HHV basis
Limit heat loadapprox. 1.3 kWa 1.5 kW class heat exchanger leaves margin

As the stack degrades, the voltage at a given current rises and the heat load rises with it. Base your design margin on the voltage limit.

Gas handling and venting

Low-current operation needs a heater

At low current, electrolysis alone does not raise the electrolyte to the recommended temperature. If you plan long periods at low current, fit a KOH-compatible heater in the tank and put temperature monitoring and over-temperature protection in your BoP.

  • OUT is a wet discharge carrying oxygen and electrolyte together. Provide gas-liquid separation and return the electrolyte to the tank.
  • Do not put any valve or device that can shut off on a vent line. The tank vent must also be non-isolable.
  • Place drain and sample ports at the lowest point of the tank.
  • Wherever a hydrogen volume can be closed off or pressurised, provide a dry nitrogen purge connection and a safe discharge path. Set purge flow and duration after reviewing the piping volume and the P&ID. Never purge with compressed air or oxygen.

First commissioning conditions

PressureAtmospheric, or close to atmospheric, on both sides
Hydrogen outletUnrestricted. Free vent
BPRFully open or bypassed

What a pressurised build must include

  • Independent anode and cathode pressure transmitters, plus a calculated differential
  • Independent high-pressure and differential-pressure shutdown interlocks
  • Automatic product-gas isolation on high pressure
  • A verified safe discharge or depressurisation path
  • A manual BPR is an adjustment component only. We do not approve it as a standalone pressure control or safety device.

Pressure limits and instrumentation

Do not read 10 barg as a differential

10 barg is the maximum hydrogen-side operating pressure. It does not mean an allowable differential of 10 bar. The anode-to-cathode pressure difference is a separate item — read it together with the undetermined section below.

Measured at full load under pressure

The control limit is 2 vol% hydrogen in oxygen (H₂-in-O₂). The figures below are measured over the window of a separate 10 barg run for which gas analysis records exist.

Recorded window189.5 hthe window for which gas analysis records exist
H₂-in-O₂ average1.006 vol%1.435 vol% maximum over the same window
Control limit2 vol%we recommend stopping above this

Crossover rises at part load

These multipliers come from 49 measured points between ambient pressure and 6 barg. The multiplier held consistent regardless of pressure.

Full load1× referencecontrol limit is 2 vol% H₂-in-O₂
60% load1.25 to 1.43×
40% load1.67 to 1.94×below 40–50%, 2 vol% becomes the practical design limit

Mitigate with at least one of: a minimum-load limit, reduced pressure at low load, or a 2 vol% interlock.

What we have not fixed yet

There is no numerical differential-pressure limit for a standalone HXS-2 that covers both steady and transient states. Pressurised full-stack validation is in progress. Trip settings are fixed per project after reviewing transmitter range and response time, valve fail position, relief arrangement and enclosed gas volume against the P&ID. Do not carry system-level (HXB-V1) alarm values over to a standalone stack as differential-pressure limits.

Minimum instrumentation by location

LocationInstrumentation
TankLevel, temperature, non-isolable vent, drain and sample at the lowest point
Stack inletTemperature downstream of the heat exchanger, flow
Stack outletOutlet temperature, KOH-compatible anode pressure
Hydrogen outletCathode pressure immediately after the stack and upstream of any regulator or valve. We recommend a secondary pressure downstream of the BPR as well
External controllerFlow, both pressures, stack current and voltage, tank/inlet/outlet PT100, level, leak, emergency stop and valve feedback, pump and power commands, isolation and vent outputs, hard-wired emergency stop

HXS-2 has no onboard PLC and no standard communication interface. An external controller provides the functions above.

Commissioning sequence

Detailed procedures for each step and the full first-run checklist are in chapter 6 of the user manual.

  1. Confirm atmospheric pressure on both sidesCheck that the hydrogen outlet is open and the BPR is open or bypassed.
  2. Fill electrolyte and check for leaksFill the tank, circulate, and inspect every joint.
  3. Set flow and temperatureSet 4 L/min and verify the recommended temperature. Use a heater if you are running at low current.
  4. Connect DC and ramp up from low currentRaise the current in steps while watching voltage and temperature.
  5. First-run checksCheck voltage behaviour, leaks, temperature and gas discharge. Follow the items in manual section 6-5.

Where maintenance ends and disassembly begins

  • MEA replacement is a return service. Send us the stack and we replace the MEA only. End plates, bipolar plates, cell frames and fasteners are reused.
  • Disassembling it yourself requires a 5-tonne hydraulic press. The bolting procedure is in the assembly guide.
  • We do not warrant performance or leak-tightness after disassembly. Read this together with the warranty and service policy.
  • There is no fixed electrolyte replacement interval. What is consumed in operation is water; the KOH itself is not consumed. Stop and inspect, then replace, when H₂-in-O₂ exceeds the control limit or when electrolyte condition and performance trend change.
  • Other periodic inspection items are in chapter 7 of the manual.

Take the PDF

The same content as a document, Korean and English, no email form. Eight pages.

HX-SIG-HXS2-EN-001 · Rev 02 · 2026-08-23

This document is a design reference. Where an individual contract specifies something different, the contract prevails.

Working through your own BoP design?

Tell us your operating conditions and the constraints you are designing against. The engineer who built the stack will answer.